Shelly Fan Control Agent Documentation

This directory manages the configuration, code templating, and deployment for the Shelly Plug S (Gen 3) that controls the cellar ventilation fan to prevent mold.

Domain Structure & Key Files

  • main.tf: Coordinates rendering the JavaScript template and executing the Python upload script.
  • variables.tf: Defines MAC addresses for the Bluetooth sensors, safety parameters, and the mold calculation coefficients.
  • scripts/Taupi-4.0.js: The source Shelly control script containing the logic for parsing Bluetooth BTHome events, calculating dew points, evaluating mold danger, and switching the relay.
  • scripts/Taupi-4.0.templated.js: The locally generated script rendering the variables passed from Terraform. Do not edit directly.
  • scripts/upload.py: Helper script executing during terraform apply to upload the templated script to the Shelly device over local HTTP RPC commands.

Architecture Decisions & Logic Gates

The ventilation controller uses a modular logic-gate architecture designed to keep the cellar dry while preventing cellar overheating in summer and overcooling in winter.

1. Decoupled Mold Alert (Sedlbauer LIM I)

To distinguish between routine/proactive drying and genuine mold risk, the mold alert (taupi_is_critical metric \rightarrow Prometheus alert TaupiFanMoldDanger) is decoupled from the fan start threshold:

  • LIM I Baseline: RH_{crit}(T) = 80\% - 0.5 \cdot (T - 10)
  • Alert Activation: RH_{in} \ge RH_{crit}(T) - \text{critical\_humi\_buffer}
  • Behavior: Fires an alert only when humidity poses an actual germination hazard on cold outer walls.

2. Cellar Overheating Prevention

In warm months, blowing outdoor air into a cool cellar can heat up the cellar mass.

  • Ceiling Protection: If T_{in} \ge 20^\circ\text{C}, the fan is only permitted to run if outdoor air is cooler than inside (T_{out} \le T_{in}).
  • Warming Allowance: If T_{in} < 20^\circ\text{C}, gentle warming is permitted, but outdoor temperature cannot exceed 20^\circ\text{C} (T_{out} \le 20^\circ\text{C}).

3. Seasonal Target Humidities

  • Cold / Winter Mode (T_{in} < 14^\circ\text{C} or T_{out} < 10^\circ\text{C}): Targets 50% RH. Once 50% RH is reached, the fan stops to preserve cellar warmth.
  • Warm / Summer Mode: Targets 40% RH for maximum drying.
  • Hard Cold Floor: The fan is blocked if T_{in} \le \text{mindesttemperatur} (default 10°C).

4. 2-Tier Scheduling & Optimal Night Window

In Central Europe / Germany, the diurnal temperature and absolute humidity minimum occurs in early morning (~03:00–07:00, peak around 05:00):

  • Urgent Drying (RH_{in} > 60\%): Runs 24/7 whenever psychrometric and temperature guards allow.
  • Routine Drying (40\% \le RH_{in} \le 60\%): Restricted to the optimal night window (03:00–07:00) to exploit maximum dew point spread.

5. Duty Cycle & Thermal Equilibrium

To allow cellar air and thermal wall mass to equilibrate and prevent non-stop continuous blowing:

  • Max Continuous Runtime: 90 minutes.
  • Cooldown Rest: 45 minutes pause after hitting max continuous runtime.

Logic Gate Summary

                      [ Telemetry Fresh & Valid? ]
                                   │ YES
                      [ Cooldown Rest Elapsed? ]
                                   │ YES
                      [ Cellar Temp > Min Floor (10°C)? ]
                                   │ YES
                      [ Overheating Safe (Tout vs Tin)? ]
                                   │ YES
                      [ Cellar RH > Target (40% / 50%)? ]
                                   │ YES
                      [ Dew Point Spread > Threshold (2°C)? ]
                                   │ YES
                      [ Urgent (>60%) OR Night Window (03-07)? ]
                                   │ YES
                          ┌────────┴────────┐
                          ▼                 ▼
                   [ START BLOWER ]   [ LOG REASON ]

Sources & References